Your shopping cart is empty!
ASTM International, 05/01/2015
Publisher: ASTM
File Format: PDF
$29.00$58.00
Published:01/05/2015
Pages:7
File Size:1 file , 120 KB
Note:This product is unavailable in Russia, Ukraine, Belarus
1.1 This specification covers the composition, sizes, dimensions, and physical properties of cellular glass thermal insulation intended for use on surfaces operating at temperatures between −450 and 800°F (−268 and 427°C). It is possible that special fabrication or techniques for pipe insulation, or both, will be required for application in the temperature range from 250 to 800°F (121 to 427°C). Contact the manufacturer for recommendations regarding fabrication and application procedures for use in this temperature range. For specific applications, the actual temperature limits shall be agreed upon between the manufacturer and the purchaser.
1.2 It is anticipated that single-layer pipe insulation in half sections or the inner layer of a multilayer system have the potential to exhibit stress cracks above 250°F (122°C).
1.3 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
Standard Test Method for Silanes Used in Rubber Formulations (bis-(triethoxysilylpropyl)sulfanes): Characterization by High Performance Liquid Chromatography (HPLC)
$25.00 $50.00
Standard Specification for Dimensions of Knife-Edge Flanges
$21.00 $42.00
Standard Test Method for Carbon Black-Void Volume at Mean Pressure
Standard Specification for Castings, Steel and Alloy, Common Requirements, for General Industrial Use
$33.00 $67.00