Your shopping cart is empty!
ASTM International, 05/01/2006
Publisher: ASTM
File Format: PDF
$33.00$67.00
Published:01/05/2006
Pages:11
File Size:1 file , 170 KB
Note:This product is unavailable in Russia, Ukraine, Belarus
1.1 This test method covers the laboratory testing of some of the acoustical properties of sound attenuating devices including duct liner materials, integral ducts, and in-duct absorptive straight and elbow silencers used in the ventilation systems of buildings. Procedures are described for the measurement of acoustical insertion loss, airflow generated noise, and pressure drop as a function of airflow.
1.2 Excluded from the scope are reactive mufflers and those designed for uses other than in ventilation systems, such as automobile mufflers.
1.3 This test method includes a provision for a simulated semi-reflective plenum to fit around thin-walled duct and silencer test specimens, since the acoustical environments around such thin-walled specimens can affect the measured insertion loss.
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.4 This method tests the performance of the specimen in well-defined and controlled conditions. If the specimen is installed in the field in any different manner, the results may be different. This standard does not provide estimating procedures for determining the actual installed performance of the specimen field conditions.
Standard Test Method for Resistance of Concrete to Rapid Freezing and Thawing
$30.00 $60.00
Standard Test Method for High Speed Puncture Properties of Plastics Using Load and Displacement Sensors
$29.00 $58.00
Standard Guide for Field Measurements of Airborne Sound Insulation of Building Facades and Facade Elements
$32.00 $65.00
Standard Specification for Fiber-Reinforced Concrete