1.1 These specifications cover the equipment making up the temporary grounding system used on de-energized electric power lines, electric supply stations, and equipment.

1.2 It is common practice for the users of protective grounding equipment to prepare complete instructions and regulations to govern in detail the correct use and maintenance of such equipment.

1.3 The uses and maintenance of this equipment are beyond the scope of these specifications.

1.4 These specifications for a system of protective grounding utilizing copper cables are covered in four parts, as follows:

 

 

 

 

 

Sections

Clamps for Temporary Protective Grounds

 

4 - 16

Ferrules for Temporary Protective Grounds

 

17 - 30

Cables for Temporary Protective Grounds

 

31 - 39

Protective Grounds (Complete Assembly With Clamps, Ferrules,   and Cable)

 

40 - 52

1.5 Each of the four parts is an entity of itself, but is listed as a part of the system for completeness and clarification.

1.6 Currents presented in Table 1 are based upon cable melting times, as determined from equations by I. M. Onderdonk and are to used in situations involving an asymmetry value less than 20 % (X/R 1.8). See Appendix X3.

(A) Withstand and ultimate short circuit properties are based on performance with surges not exceeding 20 % asymmetry factor (see 9.1 and 12.3.4.2).
(B) Yield shall mean no permanent deformation such that the clamp cannot be reused throughout its entire range of application.
(C) Ultimate rating represents a symmetrical current which the assembly or individual components shall carry for the specified time.
(D) Ultimate values are based upon application of Onderdonk's equation to 98 % of nominal circular mil area allowed by Specifications B172 and B173.

Note 1: TPG testing is done on complete assemblies. Assembly ratings assume the grade of lowest graded component (see 43.1.6).

1.6.1 Currents presented in Table 2 are based upon the values from EPRI Project RP2446 Computer Program RTGC “A Desktop Computer Program for Calculating Rating of Temporary Grounding Cables” and are to be used in situations involving an asymmetry value greater then 20 % (X/R 1.8), see Appendix X4.

Note 1: The above current values are based on electromechanical test values.

More ASTM standard pdf

ASTM F835M-00

ASTM F835M-00

Standard Specification for Alloy Steel Socket Button and Flat Countersunk Head Cap Screws [Metric]

$29.00 $58.00

ASTM D2349-90(2009)

ASTM D2349-90(2009)

Standard Test Method for Qualitative Determination of Nature of Solvent Composition in Solvent-Reducible Paints

$26.00 $52.00

ASTM D3929-03(2010)e1

ASTM D3929-03(2010)e1

Standard Test Method for Evaluating Stress Cracking of Plastics by Adhesives Using the Bent-Beam Method

$26.00 $52.00

ASTM D5072-09

ASTM D5072-09

Standard Test Method for Radon in Drinking Water

$30.00 $60.00